Yes, it has; but there is no LED indication for PF. One of our customer is confused whether it has PF or not as there is no indication for PF in meter. So, here is the Video (with / without load) for reference.
Solution: PF value depends on current and voltage phase angle. First, check the voltage Phase angle in the meter it should be 0, 120, 240. and verify the CT and PT connection in meter accordingly RYB. An issue on the site: PF value does not change ...
Please find the below images of the EN meter display to understand the situation of a meter. As shown in the above images we can see in the Y phase PF & KW is very less compare to the other two-phase. Here KW depends on the PF value because of PF ...
Please find the below image of the backside of ADC & VDC. the input of ADC and VDC is shown in SR No sticker it should be selected by the customer as per requirement. Vin or I/P will be shown in Sr no sticker. Standard input and programming range is ...
When KVA value reaches maximum value, meter will automatically reset to 0. When the meter resets, balance is also reducing which should not happen. In such case, firmware needs to be updated (to version 3.09) in that prepaid meter. Note: This is ...