4.8.2 General queries
Article: iACCL M300L modbus register
Please go through the attachment.
Article4.8.2.14S : Voltage error (V Err) on ACCL M300 3Phase
Please find the attached video herewith. At Incoming EB power supply is healthy but ACCL not sensing it and transferred to DG. As there is no DG incoming supply ACCL shows the voltage error and not giving output. If this error comes at DG incoming ...
Article 4.8.2.0 : Why 100A ACCL Trip with over Amp at 55A load?
Please find the attached video on the same. As shown in video there is more than 99A current shows in a An neutral. If it will cross more than 100 it will trip by Over Current Error. What is neutral Current in the 3Phase system? In a perfectly ...
Article 4.8.2B : iACCL - Info
40A AC1 is equal to 25A AC3 63A AC1 is equal to 40A AC3 80A AC1 is equal to 63A AC3 But our product has AC3 protection curve in our AC1 rated ACCL. For example, if you buy 40A AC1 rated 3 phase ACCL, if some one has 0.5 PF, it will trip at 25A which ...
Article 4.8.2A : iACCL - Queries
Q,1) Regarding iACCL meter, needs clarification , From EB R,Y,B & N given to input of our ACCL, Suddenly one of the phase (R,Y,B ) get failure in supply ,What will be the our ACCL action, either Trip the system or not. effect to next stage or ...