LG 6400DMC not showing the instant demand value Step-1:- Check the CT connection in the meter in Watts Parameter Like the image shown below STEP-2:- If the CT Get reversed means meter will shows minus in the watts parameter. If CT is get reversed ...
1. what parameters can be configured ? Total watts /total VA/AMPs Avg/Total VAr. 2. What are the usage of relay Relay 1 indicates safe condition of selected parameter. Relay 2 and 3 relays can be used for buzzer. Relay 4 can ...
Please find the below image of the backside of ADC & VDC. the input of ADC and VDC is shown in SR No sticker it should be selected by the customer as per requirement. Vin or I/P will be shown in Sr no sticker. Standard input and programming range is ...
In EN8410 DMC+RD, relays work only for Import Option Not for Exporting Option. @While Importing -Running Demand will increment based on load connecting. @While Exporting -Running Demand Won't increment based on load connecting. Hence EN8410 DMC+RD ...