If 500 device is connected to a gateway - 4 hours will be the log time interval. If 1500 device is connected to a gateway - 12 hours will be the log time interval. *** End of document ***
If Trip indication and command is displayed on the meter after manually tripped. Then Check the changeover of NO & NC of iELR with COM. If that also works then there is a problem in connected Breaker not in iELR. And, If NO & NC changeover not done ...
We can set or change the Datalog time interval through ElNet Configurator. Go to ElNet > Configurator > Tools > Backup / Others > Datalog Interval Time. After setting the data log interval time restart the ElNet service. Please find the below image ...
Only the leakage current will be shown in register address 151. Another address 149 is a dummy. 1. Current R Phase 40151 = Leakage current of iELR 2.Current Average 40149 = Dummy
Input current range from 60mA to 12A and trip time programmable from 300mS to 30Seconds. Inner diameters: 40mm,65mm,100mm,150mm ,200mm,250mm and 300mm.