Yes, we can connect 3 Phase Amp meter and KWH meter with the same CT. not need of separate CT for both meters. The same RYB CT's may connect to both meters for measurement. Please do the connection of CT to meters as explain below. R phase CT S1 ...
Consumption Load If users are metering a load that is consuming energy, seeing negative power (kW) readings would cause errors when reading the total consumed energy on the meter. Negative readings can be a result of the following: CT reversal: If ...
There is no option to set the Energy meter reset at 1 MWh. There is no option to control the Energy readings. Our meters will reset as per the below method for both Auto Scaling and Counter Mode. 1. The Reset for any Elmeasure Meter will occur at ...
Selecting the mechanical dimension of the CT CTs are available in a number of different physical sizes. The inner diameter of the CT must be large enough to fit around the conductive wire you wish to monitor. The outer dimensions must be small enough ...
Solution: PF value depends on current and voltage phase angle. First, check the voltage Phase angle in the meter it should be 0, 120, 240. and verify the CT and PT connection in meter accordingly RYB. An issue on the site: PF value does not change ...