For EN/PN above version 04.07, this updated software should be used to download the data. Click this link for software download page, http://www.elmeasure.com/resources/software
Kindly click the link below to download "Powerstudio" software for ID Logger 8000. https://drive.google.com/open?id=13qtNZtP-0H8bX_vrDAMoeXN_FhhZbqTK *** End of Article ***
Solution: PF value depends on current and voltage phase angle. First, check the voltage Phase angle in the meter it should be 0, 120, 240. and verify the CT and PT connection in meter accordingly RYB. An issue on the site: PF value does not change ...
By default, Gateway's IP address is 192.168.5.175. This G/W IP can be changed according to customer's requirements (i.e network range). In some cases, if customer lose the new IP address; they can reset the G/W IP address to default. Please find the ...
1. The Reset for EN Meter will occur at (999999 kvAH * MF ) 2. MF is taken into consideration from kW calculation 3. kW calculation = (1.732*PT pri *CT pri)/1000 PT pri, CT pri at Full scale. Same MF to be selected for both RESOLUTION & COUNTER ...