Article 4.19.1A : Enquiry about ATeS 63 Amp to Switch of the DG from 40 meter distance.

Article 4.19.1A : Enquiry about ATeS 63 Amp to Switch of the DG from 40 meter distance.

Yes you can switch on the DG from the mains of your home through our ATeS for such distance.

1. Generator to ATeS cable size recommended 2.5 sqmm copper.
2. Battery charger should be at DG set.
3. Aux supply 12VDC/24VDC is required for ATeS from Battery of Generator set.

You have to do the control wiring of 24VDC or 12VDC ffor our ATeS to switch on and off the DG set.