​ 1. Suggest some standard (ranges and) companies/product which make Class1 CTs in India which extend the input current range to 20 or 30A?
Comment: You can use any make CT's. In the market, Kalpa CT's have a good name. Based on your I/P load and cable size you can consider the CT rating For Ex: 30A/5A.

2. Is the actual current shunt voltage 1V(burden R 1Ohm?) if it is set in 1A (in the 1A/5A options)? Is there a CT already inside which takes up the value to 5A?
Comment: There is an inbuilt 5A CT's inside the meter so that you can connect meter directly if the load is under 5A.

3. In case I use an external CT, would it be better to set it in 1A range(to avoid 2 CTs) and enter the multiplying factor (say 30 for 30A CT)?
Comment: Use 5A o/p CT's for better accuracy. For Ex: 30A/5A CT's. No need to enter any multiplying factor. We have provision to enter the CT rating in our meter. So that it will display direct readings.