Article 4.15.1A : How to integrate BTU Meter in Elnet 5.3 software?

Article 4.15.1A : How to integrate BTU Meter in Elnet 5.3 software?

BTU meters measure the energy content of liquid flow in British thermal units (BTU), a basic measure of thermal energy.

Main Parameters which are to be integrated in Elnet will be 

Flow rate
Temperature (Inlet & Outlet)
Productivity (If available)
Watt
Watt-hour.

Such BTU meters are integrated in below mentioned sites

1. Sohar PLaza, Oman - March 2018 (Moxa N Port- Gateway)
2. Interglobe Noida- Jan 2019.(Elmeasure GW 1000)

Procedure for Integrations------

1. Note down the Process Parameters to be integrated in software. (Refer attachment from Inter globe site).
2. Run MODSCAN software & get confirmations on the readings appearing on screen & the readings on the display of Meter. 
3. Note down on the Starting address, Length & Data type to be implemented in Software.
4. Obtain Licence for adding BTU as Third Party Meter in Elmeasure software.
5. Inside configurator, Create Model, add the Register & Length, Create two or more blocks if required, assign Parameters according to the Register address.
6. If Parameter name to be changed, then do the same through SQL database.(ELnetDB/Tables/Parameter-name-Edit top 200 rows)
7. After all configurations, turn on Enet Service & check on the readings in Online module. 
8. Check if any Multiplication factor to be implemented in configurator according to the readings on Meter display. 

Final Note-
Do take prior permissions & guidance from Hardware & Software Design team if BTU meter to be integrated with Elm-GW 2000.