Issue: The ACCL is not having a display and when the incoming supply at ACCL EB terminal checked with multimeter not getting the proper voltage and coming 8.0 V R Phase to neutral, Y & N is 440, B & N is 440. Also checked at the incoming 4 pole MCB ...
Please find the attached video herewith. At Incoming EB power supply is healthy but ACCL not sensing it and transferred to DG. As there is no DG incoming supply ACCL shows the voltage error and not giving output. If this error comes at DG incoming ...
Line current is the current through any one line between a three-phase source and load. Phase current is the current through any one component comprising a three-phase source or load. Fig: 1 STAR connection Line & Phase relation. Fig: 2 DELTA ...
Please find the attached video on the same. As shown in video there is more than 99A current shows in a An neutral. If it will cross more than 100 it will trip by Over Current Error. What is neutral Current in the 3Phase system? In a perfectly ...